Ie 125 A, Ue AC 690 V/DC 440 V, for cylindrical fuse-links 22x58, 3-pole design, without signalling
Rated operating current | 125 A |
Rated operating voltage AC | 690 V |
Rated operating voltage DC | 440 V |
Rated impulse withstand voltage | 6 kV |
Rated thermal current | 125 A |
Rated conditional short-circuit current (RMS) AC 400 V | 100 kA |
Rated short-time withstand current / AC 690 V / 1 s | 2,5 kA |
Rated insulation voltage | AC 800 V |
Rated frequency max. | 60 Hz |
Rated frequency min. | 50 Hz |
Power losses without fuse-link / In | 7 W |
Max. power losses of the fuse-link | 10,5 W |
Electrical endurance | 200 cycles |
Simultaneously switched N conductor | NO |
Degree of protection from front side, built-in device, cover opened | IP20 |
Degree of protection from front side, built-in device, cover closed | IP20 |