The power quality analyzer and fault recorder multimess F144-PQ for low, medium and high voltage networks is the central component of a system that can be used to solve all measurement tasks in electrical networks. Detect possible malfunctions before they lead to a loss of production or defects in plant components. The multimess F144-PQ measures and monitors the network quality. It can be used as a power quality interface according to network quality standards, such as IEC61000-2-2 / EN50160 or to check technical connection guidelines, such as DIN VDE AR 4110 and DIN VDE 4120.

Distributor by
KBR

Product detail

  • Power quality according to EN 50160 and IEC 61000-2-2/2-4
  • IEC 61000-4-30 Class A
  • Fault recorder (oscilloscope, rms value, event)
  • Comfortable visualization software WinPQ/PQ
  • Control system connection (TCP/IP, IEC 61850)
  • Difference current measurement
  • Harmonic measurement up to 9 kHz optional
  • … and many other advantages
  • 5-Zoll-Color display
  • IEC 61000-4-30, Class-A-Measurement data processing
  • Recording of voltage quality incidents according to DIN EN 50160; IEC 61000-2-2; -2-12;-2-4
  • 1 GB internal memory (32GB expandable)
  • Bandwidth 20 kHz
  • Difference current measurement RCM
  • 4 Voltage inputs, Accuracy < 0,1 %
  • 5 Current inputs
  • Simultaneous processing of sampled and calculated voltages and currents
  • Voltage and current oscillograph sampling frequency: 40,96 kHz / 10,24 kHz
  • Half-cycle recorder: line frequency, rms voltages and currents (RMS), voltage and current pointers, power recording rate: ~10ms (50Hz) / ~8,33ms (60Hz)
  • Powerful triggering
Technical details multimess F144-PQ
Color display5-Zoll
Keypad for basic configuration on the deviceyes
Memory 1GB internal, up to 32GB SD cardyes
Protection typeIP 54 (in installed condition)
Voltage inputs, accuracy < 0.1 %4
Current inputs 1/5 A rated current4
Measuring channel band width 20 kHz (voltage and current)yes
ICE61000-4-30 Edition 3 Class Ayes
Residual current input RCMoptional
Temperature input PT100/PT1000yes
Digital inputs8
Digital outputs4
Voltage and current oscillograph 10.24 kHz (40.96 kHz option)yes
Online streaming of voltages and currentsyes
Voltage and current harmonics 2. – 50. Harmonicyes
Voltage and current harmonics 51. – 180. Harmonicoptional
InterfacesEthernet / RS 485
Communication protocol Modbus RTU | TCP
MountingPanel mounting, 144 x 144 mm
Dimensions L x W x H (without terminals)144 x 144 x 90 mm
Dimensions L x W x H (with terminals)144 x 180 x 110 mm
Dimensions breakout dimension (+0.8 mm)138 x 138 mm
Weight1220 g
Free evaluation software WinPQ Liteyes
MIT Maximize Integrated Technology Co.,Ltd.

MIT Maximize Integrated Technology Co.,Ltd. is a global leader in power quality, industrial automation and power control product and service solutions. Products include circuit breakers, switchgear, UPS and DC power systems, power distribution units, motor controls, meters, sensors, relays and inverters. The principal markets for the Electrical Sector are industrial, institutional, government, utility, commercial, residential, information technology, telecommunications and original equipment manufacturer customers.