MOREK Universal terminal blocks for copper and aluminium Universal terminals OTL are designed for copper and aluminium conductors. The terminals are suitable for all types of copper or aluminium conductors with cross section up to 240 mm². Multiple copper wires can be placed to the OTL terminal blocks according to the respective terminal type (see Table of universal terminals OTL wiring connectivity below). IP protection class for OTL terminals is IP20.
Universal terminals OTL are designed for copper and aluminium conductors. The terminals are suitable for all types of copper or aluminium conductors with cross section up to 240 mm². Multiple copper wires can be placed to the OTL terminal blocks according to the respective terminal type (see Table of universal terminals OTL wiring connectivity below). IP protection class for OTL terminals is IP20.
Universal terminals OTL are tested and certified by following standards:
EN 60947-7-1:2009 „Low-voltage switchgear and control gear – Part 7-1: Ancillary equipment – Terminal blocks for copper conductors“
EN 61238-1:2003 „Compression and mechanical connectors for power cables for rated voltages up to 30 kV (Um = 36 kV) – Part 1: Test methods and requirements“
All connectors used inside switchgears or similar appliances must fulfil these requirements.
Class A (heat cycle and short-circuit tested) – These are connectors intended for electricity distribution or industrial networks in which they can be subjected to short-circuits of relatively high intensity and duration. Therefore, Class A connectors are suitable for most applications. | Class B (heat cycle tests only, not short-circuit tested) – These are connectors for networks in which overloads or short-circuits are rapidly cleared by the installed protective devices, e.g. fast-acting fuses. |
For choosing safe and reliable connector, always make sure that the terminal is equipped with CE and Class A markings with the symbol of certifying institute, for example FI -mark.
Criteria Conditions | 94 V-0 | 94 V-1 | 94 V-2 |
---|---|---|---|
Total flaming combustion for each specimen | ≤ 10 sec | ≤ 30 sec | ≤ 30 sec |
Total flaming combustion for all 5 specimens of any set | ≤ 50 sec | ≤ 250 sec | ≤ 250 sec |
Flaming and glowing combustion for each specimen after second burner flame application | ≤ 30 sec | ≤ 60 sec | ≤ 60 sec |
Cotton ignited by flaming drips from any specimen | No | No | Yes |
Conductor cross section mm2 / number of wires Al/Cu | Tightening torque | In (A) | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Type | 1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | 185 | 240 | (Nm) | Al/Cu |
OTL 16 | 1/3 | 1/3 | 1/2 | 1/2 | 1/1 | 1/1 | 1,5 Nm (1,5-6 mm2) 7 Nm (10-16 mm2) | 75/82 | |||||||||
OTL 35 OTL 35-2 OTL 35-3X OTL 35-5X | 1/3 | 1/3 | 1/3 | 1/3 | 1/2 | 1/1 | 1/1 | 3 Nm (2,5-16 mm2) 6 Nm (25-35 mm2) | 120/135 | ||||||||
OTL 50 OTL 50-2 OTL 50-3 | 1/3 | 1/3 | 1/3 | 1/3 | 1/3 | 1/3 | 1/2 | 1/1 | 1/1 | 1,5 Nm (1,5 – 2,5 mm2) 5 Nm (4-10 mm2) 10 Nm (16-50 mm2) | 145/160 | ||||||
OTL 95 OTL 95-2 OTL 95-3 | 1/3 | 1/3 | 1/3 | 1/3 | 1/2 | 1/1 | 1/1 | 1/1 | 12 Nm (6-25 mm2) 22 Nm (35-95 mm2) | 220/245 | |||||||
OTL 150 OTL 150-2 OTL 150-3 | 1/3 | 1/3 | 1/3 | 1/2 | 1/1 | 1/1 | 1/1 | 14 Nm (25-50 mm2) 30 Nm ( 70-150 mm2) | 290/320 | ||||||||
OTL 240 OTL 204-2 | 1/3 | 1/3 | 1/3 | 1/2 | 1/2 | 1/1 | 1/1 | 1/1 | 26 Nm (35-120 mm2) 40 Nm (150-240 mm2) | 380/425 |